In this video I will find the line-urrent=? of a 2-load 3-phase system. Load 1 draws 30kW (real power) with a power factor, PF=0.6, which is lagging, and load 2 draws 45kVAR (reactive power) with a power factor, PF=0.8, which is lagging. Therefore we will have to adjust for that by writing the actual complex power equation with the real part and the reactionary part.